IPP Software Navigation Tools IPP Links Communication Pan-STARRS Links

Changes between Version 35 and Version 36 of PS1_IPP_Czarlog_20190510


Ignore:
Timestamp:
May 16, 2019, 3:27:39 PM (7 years ago)
Author:
tdeboer
Comment:

--

Legend:

Unmodified
Added
Removed
Modified
  • PS1_IPP_Czarlog_20190510

    v35 v36  
    12421242Bank(B): Current(Normal):  10.0 A       Max Detected: 12.7 A
    12431243Temperature-Internal(T1):  51.9°C(125.3°F)      Max Detected: 53.9°C(128.9°F)
    1244 }}}
     1244
     124514:00:
     1246i06pdu2:
     1247PDU Current(Normal):  20.8 A    Max Detected: 32.1 A
     1248Bank(A): Current(Normal):  12.9 A       Max Detected: 17.9 A
     1249Bank(B): Current(Normal):  7.9 A        Max Detected: 14.7 A
     1250Temperature-Internal(T1):  49.9°C(121.7°F)      Max Detected: 51.9°C(125.3°F)
     1251
     1252i06pdu1:
     1253PDU Current(Normal):  19.8 A    Max Detected: 28.4 A
     1254Bank(A): Current(Normal):  11.1 A       Max Detected: 16.1 A
     1255Bank(B): Current(Normal):  8.3 A        Max Detected: 12.7 A
     1256Temperature-Internal(T1):  50.9°C(123.5°F)      Max Detected: 53.9°C(128.9°F)
     1257
     125814:30:
     1259i06pdu2:
     1260PDU Current(Normal):  24.8 A    Max Detected: 32.1 A
     1261Bank(A): Current(Normal):  15.2 A       Max Detected: 17.9 A
     1262Bank(B): Current(Normal):  9.7 A        Max Detected: 14.7 A
     1263Temperature-Internal(T1):  50.9°C(123.5°F)      Max Detected: 51.9°C(125.3°F)
     1264
     1265i06pdu1:
     1266PDU Current(Normal):  23.3 A    Max Detected: 28.4 A
     1267Bank(A): Current(Normal):  12.9 A       Max Detected: 16.1 A
     1268Bank(B): Current(Normal):  10.0 A       Max Detected: 12.7 A
     1269Temperature-Internal(T1):  51.9°C(125.3°F)      Max Detected: 53.9°C(128.9°F)
     1270
     127115:30:
     1272i06pdu2:
     1273PDU Current(Normal):  24.1 A    Max Detected: 32.1 A
     1274Bank(A): Current(Normal):  15.0 A       Max Detected: 17.9 A
     1275Bank(B): Current(Normal):  9.5 A        Max Detected: 14.7 A
     1276Temperature-Internal(T1):  50.9°C(123.5°F)      Max Detected: 51.9°C(125.3°F)
     1277
     1278i06pdu1:
     1279PDU Current(Normal):  24.2 A    Max Detected: 28.4 A
     1280Bank(A): Current(Normal):  13.8 A       Max Detected: 16.1 A
     1281Bank(B): Current(Normal):  10.1 A       Max Detected: 12.7 A
     1282Temperature-Internal(T1):  51.9°C(125.3°F)      Max Detected: 53.9°C(128.9°F)
     1283}}}
     1284 We can conclude that the current configuration (10x groups x0,x1,x2 without ippx029-036) is working well and will not trigger PDU alarms.
    12451285
    12461286 ---------